DALEMANS offers two types of control units. The analog system, ideal for car parks with up to 40 spaces, uses star wiring for the detectors. The CAN Bus system has inline cabling. In addition, it can also be equipped with a DMS remote display system.
In the event of a pre-alarm, the ventilation is activated at low speed. In the event of an alarm, the ventilation is switched over to high speed. If the concentration level increases again, the light panels and sirens are activated.
The alarm control panel complies with the EN50545-1 standard.
DALEMANS systems are designed to detect carbon monoxide, nitrogen dioxide, LPG, and CNG.
The position of the detectors is adapted according to the density of the gas. To detect carbon monoxide and nitrogen dioxide, the detectors are placed 150 cm from the ground. For LPG, the detectors will be installed 15 cm above the floor. For CNG, the detectors will be installed on the ceiling.
Directly, or through your fitter, DALEMANS carries out the start-up and maintenance of your gas detection system.
Download the complete specifications for gas detection solutions for parking applications.